Installing the Equipment
Page 2-8 Reference Guide: RX1290 H.264 Contribution Receiver
ST.RE.E10228.1
2.6 Protective Earth/Technical Earth
WARNINGS...
1. THIS UNIT MUST BE CORRECTLY EARTHED THROUGH THE MOULDED PLUG SUPPLIED.
IF THE LOCAL MAINS SUPPLY DOES NOT HAVE AN EARTH CONDUCTOR DO NOT
CONNECT THE UNIT. CONTACT CUSTOMER SERVICES FOR ADVICE.
2. BEFORE CONNECTING THE UNIT TO THE SUPPLY, CHECK THE SUPPLY REQUIREMENTS
IN ANNEX B.
The terminal marked at the rear panel is a Technical Earth. Its use is recommended. This is
NOT a protective earth for electric shock protection. The terminal is provided to:
1. Ensure all equipment chassis fixed within a rack are at the same technical earth potential.
To do this, connect a wire between the Technical Earth terminal and a suitable point on
the rack.
2. Eliminate the migration of stray charges when connecting between equipment.
The Technical Earth provides a suitable connection between the equipment and the
installation to give a low impedance path at normal operating frequencies.
Figure 2.3: Location of the Technical Earth
Technical Earth